Pitakonan sing Sering Ditakoni Babagan Teste Tahan Insulasi

Tester Resistansi Insulasi Cocog Kanggo Ngukur Nilai Resistansi Maneka Bahan Insulasi Lan Ketahanan Insulasi Transformator, Motor, Kabel Lan Peralatan Listrik, Kanggo Mesthekake Peralatan Iki, Peralatan Listrik lan Garis Bisa Ing Kondisi Normal Kanggo Nyegah Kejut Listrik, Korban lan Peralatan karusakan.
Masalah Umum Tester Resistansi Insulasi Kaya ing ngisor iki:
 
1. Nalika Ngukur Resistance Beban Kapasitif, Apa Hubungan Antarane Output Short-Circuit Current Tester Resistance Insulation Lan Data sing Diukur, Lan Kenapa?
 
Ukuran Output Arus Sirkuit Pendek Tester Resistansi Insulasi Bisa Nggambarake Ukuran Resistansi Internal Sumber Tegangan Dhuwur Nang Megger.
 
Akeh Tes Insulasi Target Beban Kapasitif, Kayata Kabel sing Luwih dawa, Motor Kanthi Winding Luwih, Lan Transformer.Mulane, Nalika Target Diukur Nduwe Kapasitansi, Ing Awal Proses Tes, Sumber Tegangan Tinggi Ing Tester Resistansi Insulasi Kudu Ngisi Kapasitor Liwat Resistansi Internal, lan Ngisi Daya Tegangan Kanggo Output Tegangan Tinggi Tambahan Saka Insulation Resistance Tester..Yen Nilai Kapasitansi Target sing Diukur Gedhe, Utawa Resistansi Internal Sumber Tegangan Tinggi Gedhe, Proses Ngisi Daya Bakal Luwih Suwi.
 
Dawane Bisa Ditemtokake Kanthi Produk R Inner Lan C Load (Unit: Second), Yaiku T=R Inner*C Load.
 
Mula, sajrone Tes, Sampeyan Perlu Ngisi Beban Kapasitif Kaya kasebut menyang Tegangan Tes, Lan Kacepetan Ngisi Daya DV/Dt Padha karo Rasio Arus Pengisian I Kanggo Kapasitansi Beban C. Yaiku DV/Dt= I/C.
 
Mulane, sing luwih cilik Resistance Internal Lan Arus Pangisian Daya Luwih Cepet Hasil Tes Bakal Stabil.
 
2. Apa Fungsi Sisih "G" saka Penampilan?Ing Lingkungan Tes Tegangan Dhuwur lan Ketahanan Dhuwur, Yagene Dibutuhake Sambungake Terminal "G" Eksternal?
 
Ujung "G" Ing Lumahing Iku Terminal Shielding.Fungsi Terminal Shielding Yaiku Kanggo Mbusak Pengaruh Kelembapan Lan Reget Ing Lingkungan Tes Ing Asil Pangukuran.Terminal "G" Eksternal Nglewati Arus Kebocoran Produk sing Dites, Supaya Arus Bocor Ora Ngliwati Sirkuit Uji Eksternal, Lan Ngilangi Kesalahan Sing Disebabake Arus Bocor.Terminal G Digunakake Nalika Nguji Resistansi Dhuwur.
 
Umumé, Terminal G Bisa Dianggep Luwih Luwih saka 10G.Nanging, Rentang Resistance Iki Ora Pasti.Yen Resik Lan Garing Lan Volume Obyek Tes Cilik, Bisa Stabil Tanpa Ukur 500G Ing Ujung G.Ing Lingkungan Asor Lan Reged, Nilai Ketahanan sing luwih murah uga mbutuhake G End.Khusus, Yen Sampeyan Nemokake Asil Iku angel stabil nalika ngukur resistensi sing luwih dhuwur, sampeyan bisa nimbang nggunakake terminal G.Uga Wigati Terminal G Shielding Ora Disambungake menyang Lapisan Shielding, Nanging Kanggo Insulator Antarane L lan E Utawa Kanggo Kawat Multi-Stranded, Ora Kanggo Kabel Liyane Ing Test.
 
3. Kenapa Ora Mung Dibutuhake Kanggo Ngukur Nilai Resistansi Murni Nalika Ngukur Insulasi, Nanging Uga Kanggo Ngukur Rasio Penyerapan lan Indeks Polarisasi.Apa Titik?
PI minangka indeks polarisasi, sing nuduhake perbandingan antarane resistensi isolasi 10 menit lan resistensi isolasi 1 menit sajrone tes isolasi;
 
DAR yaiku rasio panyerepan dielektrik, sing nuduhake perbandingan antara resistensi isolasi 1 menit lan resistensi isolasi 15 detik sajrone tes isolasi;
 
Ing Tes Insulasi, Nilai Resistansi Insulasi Ing Momen Tertentu Ora Bisa Nggambarake Fungsi Insulasi Sampel Tes.Iki Amarga Loro Alasan Ing ngisor iki.Ing sisih siji, resistensi insulasi saka fungsi sing padha saka bahan insulasi cilik nalika volume gedhe., Ketahanan Insulasi Katon Nalika Volume Cilik.Ing sisih liya, Bahan Insulasi Nduwe Proses Rasio Penyerapan Lan Proses Polarisasi Pengisian Sawise Tegangan Dhuwur Ditrapake.Mula, Sistem Daya Mbutuhake Pangukuran Rasio Penyerapan-Rasio R60s Lan R15s, Lan Indeks Polarisasi-Rasio R10min Lan R1min Ing Tes Insulasi Transformator Utama, Kabel, Motor lan Akeh Acara Liyane, Lan Gunakake Iki Data Kanggo Nemtokake Isolasi Apik utawa Ala.
 
4. Yagene Tester Resistansi Insulasi Elektronik Bisa Ngasilake Tegangan Tinggi DC sing Luwih Dhuwur Nalika Didhukung dening Sawetara Baterei?Iki Adhedhasar Prinsip Konversi DC.Tegangan Pasokan Daya Ngisor Diunggahake Dadi Tegangan DC Output Luwih Liwat Pemrosesan Sirkuit Boost.Tegangan Dhuwur Dihasilake Luwih Inggil Nanging Daya Outpute Cilik (Energi Kurang Lan Arus Cilik).
 
Cathetan: Sanajan Kekuwatane Cilik Banget, Ora Disaranake Nyentuh Probe Tes Pribadi, Isih Ana Sensasi Tingling.

Wektu kirim: Feb-06-2021